PCD8.K120 doesn't work after FW download to PCD3

FAQ #100524

A firmware bug in version 018 does disable the power supply for the PCD8.K120 (Profi-S-Link cable) after a firmware download. A reboot of the controller is needed in order to get the adapter running again.

 

Symptom
After a firmware download to the PCD3.Mxxx0 the Profi-S-Link adapter doesn't work. No online connection over this cable is possible any more until the PCD3 is rebooted.

 

Reason
This is a bug of the firmware version 018 for the PCD3.

Solution
Upgrade the firmware to the next version (downloadable from the support site www.sbc-support.com). In case you cannot find the firmware there, contact support@saia-pcd.com.

 

Categories

PCD8 Hardware / Kxxx

PCD3 / _Firmware Classic

Last update: 22.05.2015 13:35

First release: 06.02.2006 15:49

Views: 2131

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.

Download