Frozen PCD2/3.W3x5 and PCD2/3.W6x5 modules
FAQ #100475
From a series produced in 2005 (Date Code "05xx" and FW-Version "020"), a small percentage of modules of the mentioned types show the following problem:
- Input modules: the output values of the FBox freeze, the LED and diagnose output of the FBox indicate “no response”
- Output modules: the output values of the module freeze, the LED and diagnose output of the FBox indicate “no response”
If the problem does not appear within the first five minutes, it does not appear at all. If you have affected units, please return them for repair via your local SBC representative.
Categories
PCD2 / Wxxx
PCD3 / Wxxx
Last update: 13.04.2015 02:31
First release: 02.11.2005 15:45
Views: 3761