Multi protocol functions for Profibus DP, Profi-S-IO and Profi-S-bus using port 10 or port 2 on a PCD3.Mxxxx.
FAQ #100409
The PCD3.M3xxx, PCD3.M5xxx and PCD3.M6xxx do feature different possibilities for using the port 10 (D-Sub connector) and port 2 (terminal block).
The above mentioned port can be used for Profibus DP, Profi-S-IO or Profi-S-Bus communication. Please refer to the following table for possible usages:
Port | Profibus DP* | Profi-S-IO* | Profi-S-Bus | |
PCD3.M3xx0 | 2 | Slave | Master / Slave | Master / Slave |
PCD3.M5340 | 2 | Slave | Master / Slave | Master / Slave |
PCD3.M5440 PCD3.M5540 PCD3.M5560 | 10 | Slave | Master / Slave | Master / Slave |
PCD3.M6240 PCD3.M6340 | 2 | Slave | Master / Slave | Master / Slave |
PCD3.M6440 PCD3.M6540 PCD3.M6560 | 10 | Master | Master | Master / Slave |
2 | Slave | Master / Slave | Master / Slave |
*Please be aware that it is not possible to use Profibus DP and Profi-S-IO communication in parallel on the same port!
Profi-S-Bus communication can either be used with Profibus DP or Profi-S-IO on the same port.
Categories
PCD3 / Mxxx
Last update: 25.05.2015 07:35
First release: 10.08.2005 11:17
Views: 10274