HMI Editor and PCD3.M_ or PCD2.M480: Wrong characters are display instead of value with Format #####!

FAQ #100360

When an element is configured as Integer with the format ##### (without dot) the value of the register is wrongly displayed on the terminal. This is a FW bug in the actual version of the PCD3.M_ and PCD2.M480.

 

This problem occurs with all FW version up to:

PCD3.M_         #13         (that means also 010, #11, #12)

PCD2.M480     #23         (that means also 020, #21, #22)


Solution
Please update the firmware of your PCD to the versions listed below (or later):

  • PCD3.Mxxx0  FW 1.08.23
  • PCD2.M480:  FW 1.08.19

Categories

PCD3 / Mxxx

PCD7 / D23x

Local FAQ Deutschland / HMI Editor

PCD2 / M48x

Last update: 30.05.2015 14:37

First release: 11.05.2005 12:40

Views: 4819

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.