Why communication in Open Data Mode doesn't work?

FAQ #100348

After execution CSF the error flag is set.

 

If a channel >31 is used the new PCD3's and also PCD2's with new firmware won't work. The reason is, that the number of channels is now limited on 32 channels 0-31. It was once 128 channels. Because of that programms can work on a PCD2 and didn't work on a PCD3.

Unfortunately the programming examples in the manual 26-776 D/F/E 3 are also made with a channel >31 (50/60).

 

Categories

PG5 1.x

Last update: 31.05.2015 12:22

First release: 07.04.2005 07:53

Views: 928

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.