Why communication in Open Data Mode doesn't work?
FAQ #100348
After execution CSF the error flag is set.
If a channel >31 is used the new PCD3's and also PCD2's with new firmware won't work. The reason is, that the number of channels is now limited on 32 channels 0-31. It was once 128 channels. Because of that programms can work on a PCD2 and didn't work on a PCD3.
Unfortunately the programming examples in the manual 26-776 D/F/E 3 are also made with a channel >31 (50/60).
Categories
PG5 1.x
Last update: 31.05.2015 12:22
First release: 07.04.2005 07:53
Views: 919