SFup error "macro _HEAINI6 is not part of library" when opening Fupla Editor

FAQ #100344

When using PG5 1.3.120 and having installed the old library "Heavac Dialog", the "S-FUP Error 161: New macro name '_HEAINI6' is not part of library" could appear when opening the Fupla Editor.

 

Symptom
When opening a Fupla file, the following message is shown: "S-FUP: Error 161: New macro name '_HEAINI6' is not part of library."
§ix100212§
most likely, this message is followed with the indication that Fupla couldn't open the desired file:
§ix100213§

 

Reason
This error is caused by a bug in the library Heavac Dialog that is installed by executing the library Installer "HeaDl0D23140SP.exe". The problem only occurs if this library is installed and a new version of the Heavac library is installed, too.

Solution
The problem is easy to fix. In order to do so,

  • Open the file:
    C:\Program Files\SAIA-Burgess\PG5 1_3\Libs\App\HEAVDL0.sxg with e.g. Notepad

  • Change the line 4 from
    _Dl0Vers=_HeaIni6 to 
    _Dl0Vers=_HeaIni7
    (Don't change anything else in this file! this would lead to unpredictable behaviour of Fupla!)

  • Save the file and re-open the Fupla Editor

This problem will be fixed in the next version of the Fupla libraries.

 

Categories

Local FAQ Deutschland / HEAVAC/HLK/CVC

Local FAQ Deutschland / Fupla

Last update: 25.05.2015 13:41

First release: 24.03.2005 07:45

Views: 3066

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.