S-Bus communication with Exor terminal doesn't work!
FAQ #100307
In the Exor programming tool the S-Bus driver parameter displays what looks like Data mode parameters (Parity:no, Data bit: 8, Stop bit: 1) but in reality Parity mode is needed!
To assignate the serial port of the PCD use Sasi slave FBox with the same default Parameter that the Exor configuration S-Bus driver are:
Parity mode
9600 baudes
The S-Bus station number has to be identical in PCD HW setting as in the Exor S-Bus driver configurator.
Be also aware that the PCD wiring designation might be different that the one from foreign component:
SBC | Foreign component | |
RX | D | -RX |
/RX | /D | +RX |
TX | D | -TX |
/TX | /D | +TX |