S-Bus communication with Exor terminal doesn't work!

FAQ #100307

In the Exor programming tool the S-Bus driver parameter displays what looks like Data mode parameters (Parity:no, Data bit: 8, Stop bit: 1) but in reality Parity mode is needed!

 

To assignate the serial port of the PCD use Sasi slave FBox with the same default Parameter that the Exor configuration S-Bus driver are:

 

    Parity mode
    9600 baudes

The S-Bus station number has to be identical in PCD HW setting as in the Exor S-Bus driver configurator.

Be also aware that the PCD wiring designation might be different that the one from foreign component:

 
SBC
 
Foreign component
 
RX
 
D
 
-RX
 
/RX
 
/D
 
+RX
 
TX
 
D
 
-TX
 
/TX
 
/D
 
+TX