PCD7.D776 got blocked through programme download!

FAQ #100290

Probably through the download the FW wasn't installed properly. The terminal is blocked and stays in a loop, rebooting constantly.

 

 

Solution: After the 1st check page, when the screen displays "Wait for boot forced", press the screen in diagonal in order to put it in transfer page. Download than the programme and the firmware again!

After this operation the terminal should be return to work properly.

 

Categories

PCD7 / D7xx

Last update: 17.05.2015 23:48

First release: 05.01.2005 12:24

Views: 1380

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.