Error message on build: HMI: Wrong library version: 13000. Must be 13042 or higher

FAQ #100246

There is a wrong file SHMI.LIN in the library directory

 

The first installation CD's of PG5 1.3.100 probably have a wrong SHMI.LIN file, that creates this error on build. If you have this error: Open C:\Program Files\Saia Burgess\PG5 1_3\Libs\Std\SHMI.LIN with the Text Pad or an other editor. You have to change the line: Version=V1.3.100,13000 to : Version=V1.3.100,13100.
Afterwards it will work fine.

 