PCD7.L723
FAQ #100230
The communication with the master station doesn't work and the green LED blink!
Check the power supply! All the hardware serie up to and including V 12 are very sensible regarding the power supply level. If we have less than 24 VCA (-10%) this phenomenon occurs, it might also happens if it is within the - 10% tolerance ( for example 22 VCA). Make sure you have really 24 Volts!
The harware serie V 12 SR have a correction which solve that over sensibility problem. The new serie from v 22 are OK.
Categories
PCD7 / Lxxx
Last update: 29.05.2015 02:56
First release: 30.09.2004 08:07
Views: 1898