PCD4.M170: Port 0 doesn't work?

FAQ #100187

After import a PCD4.M145 project on a PCD4.M170, the port 0 doesn't work anymore.

The PCD4.M170 doesn't have the posibility like the PCD2.M170 to use the port 0 in RS 485 only in RS 232. Because those 2 PCD have the same FW, in order to use the port 0 on a PCD4.M170 in RS 232, it has to be configured:

In IL, the SOCL instruction is necessary

In Fupla, in the SASI Slave Fbox choose RS Typ RS 232 (not default)

 

 

 

Categories

PCD4 / Mxxx

Last update: 01.04.2015 23:41

First release: 09.07.2004 15:18

Views: 2619

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.