How many rows for a PCD2 Slave can I define in the DP slave configuration of a XX7?

FAQ #100131

Up to 13 free configurable rows for configuration of the I/O data exchange area can be inserted in "HW Config".

 

The PCD2.F770 has a limited memory area for configuration of the I/O data exchange area of 80 Bytes. Each Row in "Configuration"-tab of "DP slave properties" Window needs 5 bytes of the configuration area and 3 Empty Slots (= 15 Byte) are generated unvisible for the user. Therefore 65 Byte are left for up to 13 free configurable rows. The "DP slave properties" Window apears after a double-click on the slave-station in "HW Config" of "SIMATIC® Manager".