Is Profibus-DP master-master communication possible? How many stations are supported?

FAQ #100086

 

Yes, master-master communication is possible (FDL). Up to 126 masters can operate on the Profibus-DP network. The Profibus master module PCD7.F750 is necessary for this. The maximum number of specific FDL connections (39) in the Simatic-Manager should also be taken into account. Unspecified FDL connections can be used in addition.

 

Categories

xx7 Series / Communication

Last update: 31.05.2015 07:41

First release: 08.06.2004 14:48

Views: 3454

The requested software / document is no longer marketed by Saia-Burgess Controls AG and without technical support. It is an older software version which can be operated only on certain now no longer commercially available products.