AcknowledgeAlarm service requests, which use complete wildcards as timestamps. Main corrections All PCD’s: On S-Bus data mode, if S-Bus CRC contains a S-Bus DLE as last character then S-Bus telegram is incorrect and not accepted from S-Bus recipient. (Since FW 1.28.20) All PCD’s: Not all bytes are transmitted when working with MC4 or MC5 mode on F2xxx module All PCD’s: RS485 driver keep [...] PCD’s: Profibus communcation using onboard FDL port. The FCS test for SD2 telegram was not implemented correctly. All PCD’s: When S-Bus IP Nodelist is used it’s possible that the communication using
AcknowledgeAlarm service requests, which use complete wildcards as timestamps. Main corrections All PCD’s: On S-Bus data mode, if S-Bus CRC contains a S-Bus DLE as last character then S-Bus telegram is incorrect and not accepted from S-Bus recipient. (Since FW 1.28.20) All PCD’s: Not all bytes are transmitted when working with MC4 or MC5 mode on F2xxx module All PCD’s: RS485 driver keep [...] PCD’s: Profibus communcation using onboard FDL port. The FCS test for SD2 telegram was not implemented correctly. All PCD’s: When S-Bus IP Nodelist is used it’s possible that the communication using
AcknowledgeAlarm service requests, which use complete wildcards as timestamps. Main corrections All PCD’s: On S-Bus data mode, if S-Bus CRC contains a S-Bus DLE as last character then S-Bus telegram is incorrect and not accepted from S-Bus recipient. (Since FW 1.28.20) All PCD’s: Not all bytes are transmitted when working with MC4 or MC5 mode on F2xxx module All PCD’s: RS485 driver keep [...] PCD’s: Profibus communcation using onboard FDL port. The FCS test for SD2 telegram was not implemented correctly. All PCD’s: When S-Bus IP Nodelist is used it’s possible that the communication using
AcknowledgeAlarm service requests, which use complete wildcards as timestamps. Main corrections All PCD’s: On S-Bus data mode, if S-Bus CRC contains a S-Bus DLE as last character then S-Bus telegram is incorrect and not accepted from S-Bus recipient. (Since FW 1.28.20) All PCD’s: Not all bytes are transmitted when working with MC4 or MC5 mode on F2xxx module All PCD’s: RS485 driver keep [...] PCD’s: Profibus communcation using onboard FDL port. The FCS test for SD2 telegram was not implemented correctly. All PCD’s: When S-Bus IP Nodelist is used it’s possible that the communication using
AcknowledgeAlarm service requests, which use complete wildcards as timestamps. Main corrections All PCD’s: On S-Bus data mode, if S-Bus CRC contains a S-Bus DLE as last character then S-Bus telegram is incorrect and not accepted from S-Bus recipient. (Since FW 1.28.20) All PCD’s: Not all bytes are transmitted when working with MC4 or MC5 mode on F2xxx module All PCD’s: RS485 driver keep [...] PCD’s: Profibus communcation using onboard FDL port. The FCS test for SD2 telegram was not implemented correctly. All PCD’s: When S-Bus IP Nodelist is used it’s possible that the communication using
AcknowledgeAlarm service requests, which use complete wildcards as timestamps. Main corrections All PCD’s: On S-Bus data mode, if S-Bus CRC contains a S-Bus DLE as last character then S-Bus telegram is incorrect and not accepted from S-Bus recipient. (Since FW 1.28.20) All PCD’s: Not all bytes are transmitted when working with MC4 or MC5 mode on F2xxx module All PCD’s: RS485 driver keep [...] PCD’s: Profibus communcation using onboard FDL port. The FCS test for SD2 telegram was not implemented correctly. All PCD’s: When S-Bus IP Nodelist is used it’s possible that the communication using
corrections All PCD’s: On S-Bus data mode, if S-Bus CRC contains a S-Bus DLE as last character then S-Bus telegram is incorrect and not accepted from S-Bus recipient. (Since FW 1.28.20) All PCD’s: Not [...] implemented correctly. All PCD’s: When S-Bus IP Nodelist is used it’s possible that the communication using nodes does no more work after execute a download in run All PCD’s: XOB parameter as Registers [...] der Main CPU. Der Firmware-Update kann über eine beliebige S-Bus PGU-Verbindung erfolgen. 3. Die Firmware 1.26.xx oder neuer kann nur auf PCD3.M6860/M6880 mit Hardware Version D oder grösser
corrections All PCD’s: On S-Bus data mode, if S-Bus CRC contains a S-Bus DLE as last character then S-Bus telegram is incorrect and not accepted from S-Bus recipient. (Since FW 1.28.20) All PCD’s: Not [...] implemented correctly. All PCD’s: When S-Bus IP Nodelist is used it’s possible that the communication using nodes does no more work after execute a download in run All PCD’s: XOB parameter as Registers [...] der Main CPU. Der Firmware-Update kann über eine beliebige S-Bus PGU-Verbindung erfolgen. 3. Die Firmware 1.26.xx oder neuer kann nur auf PCD3.M6860/M6880 mit Hardware Version D oder grösser
corrections All PCD’s: On S-Bus data mode, if S-Bus CRC contains a S-Bus DLE as last character then S-Bus telegram is incorrect and not accepted from S-Bus recipient. (Since FW 1.28.20) All PCD’s: Not [...] implemented correctly. All PCD’s: When S-Bus IP Nodelist is used it’s possible that the communication using nodes does no more work after execute a download in run All PCD’s: XOB parameter as Registers [...] der Main CPU. Der Firmware-Update kann über eine beliebige S-Bus PGU-Verbindung erfolgen. 3. Die Firmware 1.26.xx oder neuer kann nur auf PCD3.M6860/M6880 mit Hardware Version D oder grösser
funktioniert. Die S-Bus-Kommunikation funktioniert gut, wenn keine Konverter dazwischen verwendet werden. Auch andere Kommunikationsprotokolle dann S-Bus wie "Modus C, Modbus" auf dem PCD2.F2xx0 und [...] Warum funktioniert meine RS-232 S-Bus-Kommunikation mit dem PCD2.F2xx0 und PCD3.F2xx-Modul nicht? (FAQ #101775) Der RS-232 S-Bus-Kommunikation kann funktioniert mit PCD2.F2xx0 oder PCD3.F2xx-Modulen bei der Kommunikation über Wandler (wie Modem oder optische Konverter) mit anderen Geräten überhaupt nicht. Auf PCD