Saia PCD® Supervisor V 2.1 / V 3.0 Patch 4.8.0.110.1.7 for BACnet
Software | V 2.1 / V 3.0 Patch 4.8.0.110.1.7 for BACnet | Saia PCD® Supervisor V 2.1 / V 3.0 Patch 4.8.0.110.1.7 for BACnet |
English: This patch solve a issue in relation to Saia PCD Supervisor installations having multiple IP Interface adapters installed. The problem could occur after a station restart, and lead to situation that the originally chosen BACnet Interface is not correctly assigned. This may be the case, if during station startup the IP Interface used for BACnet is not available (e.g. with USB-connected IP interfaces on PC platforms). In these cases, another available interface or no interface may be used for that station. Patch is working for Saia PCD Supervisor 2.1 and 3.0 Deutsch: Der Patch behebt ein Problem auf Saia PCD Supervisor-Installationen bei welchen mehrere IP-Interface-Adaptern installiert sind. Das Problem könnte nach einem Neustart der Station auftreten, und bewirken dass die ursprünglich gewählte BACnet-Schnittstelle nicht korrekt zugewiesen wird. Dies kann der Fall sein, wenn beim Stationsstart das für BACnet verwendete IP-Interface nicht verfügbar ist (z.B. bei USB-verbundenen IP-Interfaces auf PC-Plattformen). In diesen Fällen kann eine andere verfügbare Schnittstelle oder keine Schnittstelle für diese Station verwendet werden. Patch funktioniert für Saia PCD Supervisor 2.1 und 3.0
![]() |
.zip | 0.03 MB | Download |